Moderate Recalled June 19, 2007 About 3,300 units Updated May 23, 2014

Cummins Power Generation Inc. Recalls Stationary Natural Gas and Propane Fueled Generators Due to Fire Hazard

Fire

The hazard

The generator's fuel shut-off valve can fail to close, resulting in a gas leak from the unit. This poses a risk of fire and burn injuries to consumers.

Incidents reported: Cummins Power Generation has received one report that the fuel shut-off valve failed to close. No injuries or damages have been reported.

What to do now

Consumers should stop using these generators immediately, place the Operators switch in "OFF" and maintain this status until the upgrade is completed. The local distributor or dealer should be contacted to schedule a free, on-site repair by a Cummins Power Generation authorized trained technician.

Contact: For more information, contact Cummins Power Generation Inc. at (800) 888-6626, Option 3, between 8 a.m. and 5 p.m. CT Monday through Friday.

About this recall

The recall involves both commercial and residential model Cummins Power Generation gaseous-fueled stationary generator sets (fueled by propane or natural gas). They have the following model numbers listed on the generator nameplate which is located at the front base of the unit: commercial models GGDB, GGMA/B/C, and GNAA/B/C, and residential models RS15000, RS20000, and RS30000. These units also have serial number A050734102 through L068998479 and "Cummins Power Generation" listed on the generator nameplate.