Moderate Recalled January 28, 2014 About 610 units Updated May 11, 2015

System Sensor Recalls Reflected Beam Smoke Detectors Due To Failure to Alert Consumers in a Fire (Recall Alert)

Fire

The hazard

When used with certain power supplies, the reflected beam smoke detectors can fail to send a signal to the fire alarm control panel that sounds the alarm and fail to alert occupants of a fire.

Incidents reported: None reported

What to do now

Replace

Owners with the affected smoke detectors powered by a power supply that is not on the company's acceptable list available online, should contact System Sensor to receive free replacement smoke detectors. System Sensor and its distributors are contacting purchasers directly.

Contact: System Sensor at (800) 736-7672 from 7:30 a.m. through 5 p.m. CT Monday through Friday, or online at www.systemsensor.com and click on Resources, then Product Info Library/Technical Field Bulletins, then Safety Bulletins for more information and a list of acceptable power supplies.

About this recall

This recall involves System Sensor's reflected beam smoke detectors with model number BEAM1224S and date codes 2111 through 3053. The YMMW format date codes stand for (2111) 2012-November-1st week of Nov. through (3053) 2013-May-3rd week of May. The detectors are ivory and black and measure 10 inches high by 7½ inches wide. The model number and date code are printed on a label on the back of the detector's cover and on the product's packaging. The reflected beam smoke detectors were used primarily in commercial buildings as part of the fire alarm system. Detectors used with acceptable power supplies, as listed on the company website, do not need to be replaced.

Product photos

System Sensor smoke detectors
System Sensor smoke detectors
Label on System Sensor smoke detectors
Label on System Sensor smoke detectors
Label on carton for System Sensor smoke detectors
Label on carton for System Sensor smoke detectors

Photos: U.S. CPSC